Table 31.10-18(b)
Soda acid |
Discharge. Clean hose and inside of extinguisher thoroughly. Recharge. |
Foam |
Discharge. Clean hose and inside of extinguisher thoroughly. Recharge. |
Pump tank (water or antifreeze) |
Discharge. Clean hose and inside of extinguisher thoroughly. Recharge with clean water or antifreeze. |
Cartridge operated (water, antifreeze or loaded stream) |
Examine pressure cartridge and replace if end is punctured or if cartridge is otherwise determined to have leaked or to be in unsuitable condition. Remove liquid, clean hose and inside of extinguisher thoroughly. Recharge with clean water, solution, or antifreeze. Insert charged cartridge. |
Stored pressure (water, antifreeze or loaded stream) |
See that pressure gage is in operating range. If not, or if seal is broken, weigh or otherwise determine that full charge is in extinguisher. Recharge if pressure is low or if extinguishing agent is needed. |
Carbon dioxide |
Weigh cylinders. Recharge if weight loss exceeds 10 percent of weight of charge. Inspect hose and nozzle to be sure they are clear.1
|
Code of Federal Regulations
377
|
Dry chemical (cartridge-operated type) |
Examine pressure cartridge and replace if end is punctured or if cartridge is otherwise determined to have leaked or to be in unsuitable condition. Inspect hose and nozzle to see if they are clear. Insert charged cartridge. Be sure dry chemical is freeflowing (not caked) and chamber contains full charge. |
Dry chemical (stored pressure type) |
See that pressure gage is in operating range. If not, or if seal is broken, weigh or otherwise determine that full charge of dry chemical is in extinguisher. Recharge if pressure is low or if dry chemical is needed. |
Vaporizing liquid 2 (pump type) |
Pump a few strokes into clean pail and replace liquid. Keep water out of extinguisher or liquid. Keep extinguisher completely full of liquid. |
Vaporizing liquid 2 (stored pressure type) |
See that pressure gage is in operating range. Weigh or check liquid level to determine that full charge of liquid is in extinguisher. Recharge if pressure is low or if liquid is needed. |
1 Cylinders must be tested and marked, and all flexible connections and discharge hoses of semi-portable carbon dioxide and halon extinguishers must be tested or renewed, as required by §§ 147.60 and 147.65 of this chapter. |
2 Vaporizing-liquid type fire extinguishers containing carbon tetrachloride or chlorobromomethane or other toxic vaporizing liquids shall be removed from all vessels. |