132.310—Fixed fire-extinguishing systems for paint lockers.
               		
               	 	
               	 	
               	 	               	 	               	 	               	 	               	 	
               	 	
    
        
        (a) 
         Except as provided by paragraph (b) of this section, a fixed gaseous fire-extinguishing system or another approved fixed fire-extinguishing system must be installed in each paint locker.
     
    
        
        (b) 
         No fixed fire-extinguishing system need be installed in a paint locker that is—
     
    
        
        (1) 
         Less than 1.7 cubic meters (60 cubic feet) in volume;
     
    
        
        (2) 
         Accessible only from the weather deck; and
     
    
        
        (3) 
         Not adjacent to a tank for flammable or combustible liquid.
     
    
        
        (c) 
         Each fixed fire-extinguishing system installed must comply with  part 95 of this chapter or be approved by the Commanding Officer, Marine Safety Center.