111.05-31—Grounding conductors for systems.
(a)
A conductor for grounding a direct-current system must be the larger of:
(1)
The largest conductor supplying the system; or
(2)
No. 8 AWG (8.4mm 2 ).
(b)
A conductor for grounding the neutral of an alternating-current system must meet Table 111.05-31(b).
Table 111.05-31(b)—Neutral Grounding Conductor for Alternating-Current System
|
2 (33.6) |
8 (8.4) |
2 (33.6) |
0 (53.5) |
6 (13.3) |
0 (53.5) |
3/0 (85.0) |
4 (21.2) |
3/0 (85.0) |
350 MCM (177) |
2 (33.6) |
350 MCM (177) |
600 MCM (304) |
0 (53.5) |
600 MCM (304) |
1100 MCM (557) |
2/0 (67.5) |
1100 MCM (557) |
|
3/0 (85.0) |