(a)
Each inlet and outlet to a compressor or blower which handles vapor that has not been inerted, enriched, or diluted in accordance with § 154.824 of this subpart must be fitted with:
(1)
A detonation arrester;
(3)
An explosion suppression system acceptable to the Commandant (CG-522).
(b)
If a reciprocating or screw-type compressor handles vapor in the vapor collection system, it must be provided with indicators and audible and visible alarms to warn against the following conditions:
(1)
Excessive discharge gas temperature at each compressor chamber or cylinder;
(2)
Excessive cooling water temperature;
(5)
Low lube oil pressure; and
(6)
Excessive shaft bearing temperatures.
(c)
If a liquid ring-type compressor handles vapor in the vapor collection system, it must be provided with indicators and audible and visible alarms to warn against the following conditions:
(1)
Low level of liquid sealing medium;
(2)
Lack of flow of liquid sealing medium;
(3)
Excessive temperature of the liquid sealing medium;
(5)
Low lube oil pressure, if pressurized lubricating system; and
(6)
Excessive shaft bearing temperature.
(d)
If a centrifugal compressor, fan, or lobe blower handles vapor in the vapor collection system, construction of the blades and/or housing must meet one of the following:
(1)
Blades or housing of nonmetallic construction;
(2)
Blades and housing of nonferrous material;
(3)
Blades and housing of corrosion resistant steel;
(4)
Ferrous blades and housing with one-half inch or more design tip clearance; or
(5)
Blades of aluminum or magnesium alloy and a ferrous housing with a nonferrous insert sleeve at the periphery of the impeller.
Code of Federal Regulations
[CGD 88-102, 55 FR 25429, June 21, 1990, as amended by CGD 96-026, 61 FR 33666, June 28, 1996; USCG-2010-0351, 75 FR 36284, June 25, 2010]