149.409—How many fire extinguishers are needed?

Each particular location must have the number of fire extinguishers required by table 149.409.
Table 149.409—Portable and Semi-Portable Extinguishers, Minimum Quantity and Location
Space Classification Minimum quantity and location
(a) Safety Areas:
(1) Communicating corridors A-II One in each main corridor or stairway not more than 150 feet apart.
(2) Radio room C-II One outside or near each radio room exit.
(b) Accommodation Spaces:
(1) Sleeping quarters A-II One in each sleeping space that fits more than four persons.
(c) Service Spaces:
(1) Galleys B-II or CII One for each 2,500 square feet or fraction thereof, for hazards involved.
(2) Storerooms A-II One for each 2,500 square feet or fraction thereof, located near each exit, either inside or outside the space.
Code of Federal Regulations 182
(3) Paint room B-II One outside each paint room exit.
(d) Machinery Spaces:
(1) Gas-fired boilers B-II OR C-II Two.
(2) Gas-fired boilers B-V One. 1
(3) Oil-fired boilers B-II Two.
(4) Oil-fired boilers B-V Two. 1
(5) Internal combustion or gas turbine engines B-II One for each engine. 2
(6) Open electric motors and generators C-II One for each of two motors or generators. 3
(e) Helicopter Areas:
(1) Helicopter landing decks B-V One at each access route.
(2) Helicopter fueling facility B-V One at each fuel transfer facility.4
1 Not required if a fixed system is installed.
2 If the engine is installed on a weather deck or is open to the atmosphere at all times, one B-II may be used for every three engines.
3 Small electrical appliances, such as fans, are exempt.
4 Not required if a fixed foam system is installed in accordance with 46 CFR 108.489 .