Table 145.10(a)—Portable and Semi-Portable Extinguishers
safety areas
|
Communicating corridors |
A-II |
1 in each main corridor not more than 150 feet apart. (May be located in stairways.) |
Radio room |
C-II |
1 in vicinity of exit.
|
accommodations
|
Sleeping accommodations |
A-II |
1 in each sleeping accommodation space. (Where occupied by more than 4 persons.)
|
services spaces
|
Galleys |
B-II or C-II |
1 for each 2,500 square feet or fraction thereof for hazards involved. |
Storerooms |
A-II |
1 for each 2,500 square feet or fraction thereof located in vicinity of exits, either inside or outside of spaces.
|
machinery spaces
|
Gas-fired boilers |
B-II (CO2 or dry chemical) |
2 required. |
Gas-fired boilers |
B-V |
1 required. 1
|
Oil-fired boilers |
B-II |
2 required. |
Oil-fired boilers |
B-V |
2 required. 1
|
Internal combustion or gas turbine engines |
B-II |
1 for each engine. 2
|
Electric motors or generators of open type |
C-II |
1 for each 2 motors or generators. 3
|
1 Not required where a fixed carbon dioxide system is installed. |
2 When installation is on weather deck or open to atmosphere at all times 1 B-II for each three engines is allowable. |
3 Small electrical appliances, such as fans, etc., shall not be counted or used as basis for determining number of extinguishers required. |