(1)
The high-voltage cable must be guarded in the following locations:
(i)
From the power center cable coupler for a distance of 10 feet inby the power center;
(ii)
From the entrance gland for a distance of 10 feet outby the last strain clamp on the continuous mining machine; and,
(iii)
At any location where the cable could be damaged by moving equipment.
(2)
Guarding must be constructed using nonconductive flame-resistant material or grounded metal.
(b) Suspended cables and cable crossovers.
When equipment must cross any portion of the cable, the cable must be either:
(1)
Suspended from the mine roof; or
(2)
Protected by a cable crossover having the following specifications:
(i)
A minimum length of 33 inches;
(ii)
A minimum width of 17 inches;
(iii)
A minimum height of 3 inches;
(iv)
A minimum cable placement area of two and one half-inches (2 1/2 ″) high by four and one-quarter inches (4 1/4 ″) wide;
(v)
Made of nonconductive material;
(vi)
Made of material with a distinctive color. The color black must not be used; and
(vii)
Made of material that has a minimum compressive strength of 6,400 pounds per square inch (psi).
Code of Federal Regulations
[75 FR 17549, Apr. 6, 2010]