75.601-3—Short circuit protection; dual element fuses; current ratings; maximum values.
Dual element fuses having adequate current-interrupting capacity shall meet the requirements for short circuit protection of trailing cables as provided in § 75.601, however, the current ratings of such devices shall not exceed the maximum values specified in this section:
| 14 |
|
|
15 |
15 |
| 12 |
|
|
20 |
20 |
| 10 |
|
|
25 |
25 |
| 8 |
60 |
60 |
50 |
50 |
| 6 |
85 |
90 |
65 |
70 |
| 4 |
110 |
110 |
90 |
90 |
| 3 |
130 |
150 |
105 |
110 |
| 2 |
150 |
150 |
120 |
125 |
| 1 |
170 |
175 |
140 |
150 |
| 1/0 |
200 |
200 |
170 |
175 |
| 2/0 |
235 |
250 |
195 |
200 |
| 3/0 |
275 |
300 |
225 |
225 |
| 4/0 |
315 |
350 |
260 |
300 |
| 250 |
350 |
350 |
285 |
300 |
| 300 |
395 |
400 |
310 |
350 |
| 350 |
445 |
450 |
335 |
350 |
| 400 |
480 |
500 |
360 |
400 |
| 450 |
515 |
600 |
385 |
400 |
| 500 |
545 |
600 |
415 |
450 |