(a)
A methane detector component shall be suitably constructed for incorporation in or with permissible and approved equipment that is operated in gassy mines and tunnels.
(b)
A methane detector shall include:
(1)
A method of continuous sampling of the atmosphere in which it functions.
(2)
A method for actuating a warning device which shall function automatically at a methane content of the mine atmosphere between 1.0 to 1.5 volume percent. The warning device shall also function automatically at all higher concentrations of methane in the mine atmosphere.
(3)
A method for actuating a power-shutoff component, which shall function automatically when the methane content of the mine atmosphere is 2.0 volume percent and at all higher concentrations of methane.
(4)
A suitable filter on the sampling intake to prevent dust and moisture from entering and interfering with normal operation.
Code of Federal Regulations
Note:
This requirement for the methane detector may be waived if the design is such as to preclude the need of a filter.
(c)
A methane detector may provide means for sampling at more than one point; provided, the methane detector shall separately detect the methane in the atmosphere at each sampling point with, in MSHA's opinion, sufficient frequency.