Voltage range (phase-to-phase) kilovolts | Distance in feet and inches for maximum voltage | |
---|---|---|
Phase to ground | Phase to phase | |
2.1 to 15 | 2′0″ | 2′0″ |
15.1 to 35 | 2′4″ | 2′4″ |
35.1 to 46 | 2′6″ | 2′6″ |
46.1 to 72.5 | 3′0″ | 3′0″ |
72.6 to 121 | 3′4″ | 4′6″ |
138 to 145 | 3′6″ | 5′0″ |
161 to 169 | 3′8″ | 5′6″ |
230 to 242 | 5′0″ | 8′4″ |
345 to 362 | 1 7′0″ | 1 13′4″ |
500 to 552 | 1 11′0″ | 1 20′0″ |
700 to 765 | 1 15′0″ | 1 31′0″ |
1 For 345-362kv., 500-552kv., and 700-765kv., the minimum clearance distance may be reduced provided the distances are not made less than the shortest distance between the energized part and a grounded surface. |