Voltage(nominal, kV, alternating current) | Minimum clearance distance(feet) |
---|---|
up to 50 | 10 |
over 50 to 200 | 15 |
over 200 to 350 | 20 |
over 350 to 500 | 25 |
over 500 to 750 | 35 |
over 750 to 1,000 | 45 |
over 1,000 | (as established by the utility owner/operator or registered professional engineer who is a qualified person with respect to electrical power transmission and distribution). |
Note: The value that follows “to” is up to and includes that value. For example, over 50 to 200 means up to and including 200kV. |