433.5—Performance level determination.

(a) Each Federal agency shall determine energy consumption levels for both the baseline building and proposed building by using the Performance Rating Method found in Appendix G of ANSI/ASHRAE/IESNA Standard 90.1-2004, Energy Standard for Buildings Except Low-Rise Residential Buildings, January 2004 (incorporated by reference, see ( 433.3), except the formula for calculating the Performance Rating in paragraph G1.2 shall read as follows:
Percentage improvement = 100 x (Baseline building consumption—Proposed building consumption)/ (Baseline building consumption—Receptacle and process loads).
(b) Each Federal agency shall consider laboratory fume hoods and kitchen ventilation systems as part of the ASHRAE-covered HVAC loads subject to the 30 percent savings requirements, rather than as process loads.
Tips