431.304—Uniform test method for the measurement of energy consumption of walk-in coolers and walk-in freezers.
(a) Scope.
This section provides test procedures for measuring, pursuant to EPCA, the energy consumption of refrigerated bottled or canned beverage vending machines.
(b) Testing and Calculations.
(1)
[Reserved]
(2)
The R value shall be the 1/K factor multiplied by the thickness of the panel.
(3)
The K factor shall be based on ASTM C518 (incorporated by reference; see § 431.303 ).
(4)
For calculating the R value for freezers, the K factor of the foam at 20 degrees Fahrenheit (average foam temperature) shall be used.
(5)
For calculating the R value for coolers, the K factor of the foam at 55 degrees Fahrenheit (average foam temperature) shall be used.